Wholesale Dealers of Single Phase Load Bank - Neutral Grounding Resistor, NGR EGR – Wepower
Wholesale Dealers of Single Phase Load Bank - Neutral Grounding Resistor, NGR EGR – Wepower Detail:
█ Product Features
1. Voltage range:0.33 ~110KV
2. Rated Current: 1~5000A
3. Resistance Range:0.1Ω∽1500Ω
4. Working time: 5s,10s,30s,60s,10mins,working continuous
5. Ingress Protection:IP20~IP55
6. Installation:Indoor、Outdoor;
7. Auxiliary parts: disconnecting switch, circuit breaker, CT, PT etc.
8. Resistor temperature rise:
1)Rated time :10s, maximum temperature rise≤760K;
2)Rated time : 10s<t<10mins, maximum temperature rise ≤610K;
3)Working continuous, maximum temperature rise ≤385K;
█ Wire Diagram
The electrical connection mode between neutral point three-phase AC power grid and earth, called grounding mode for neutral point. Neutral point grounding resistor principle diagram as follows:
Neutral point of transformer, the grounding resistor has two ways:
On the secondary side the transformer is a star connection method, the neutral point grounding resistor straight. (see Figure.1)
On the secondary side the transformer is a triangle connection method, the neutral point grounding transformer grounding through grounding transformer. (see Figure. 2)
█ Production Selection Table
6.3KV series neutral grounding resistor selection table, as following:
Type |
Neutral Voltage |
Resistance |
Fault Current |
Rated Time |
Protection Class |
Enclosure |
|||
Line Voltage |
Phase Voltage |
Length |
Width |
High |
|||||
KV |
KV |
[Ω] |
[A] |
[s] |
IP |
[mm] |
[mm] |
[mm] |
|
TNGR |
6.3 |
3.64 |
72.8 |
50 |
10 |
IP2X |
800 |
1000 |
1180 |
TNGR |
6.3 |
3.64 |
36.4 |
100 |
10 |
IP2X |
800 |
1000 |
1180 |
TNGR |
6.3 |
3.64 |
18.2 |
200 |
10 |
IP2X |
800 |
1000 |
1180 |
TNGR |
6.3 |
3.64 |
14.6 |
250 |
10 |
IP2X |
800 |
1000 |
1180 |
TNGR |
6.3 |
3.64 |
12.1 |
300 |
10 |
IP2X |
800 |
1000 |
1180 |
TNGR |
6.3 |
3.64 |
9.1 |
400 |
10 |
IP2X |
1000 |
1000 |
1180 |
TNGR |
6.3 |
3.64 |
7.3 |
500 |
10 |
IP2X |
1000 |
1000 |
1180 |
TNGR |
6.3 |
3.64 |
6.1 |
600 |
10 |
IP2X |
1000 |
1000 |
1180 |
TNGR |
6.3 |
3.64 |
4.6 |
800 |
10 |
IP2X |
1000 |
1000 |
1180 |
TNGR |
6.3 |
3.64 |
3.6 |
1000 |
10 |
IP2X |
1000 |
1000 |
1180 |
TNGR |
6.3 |
3.64 |
3.0 |
1200 |
10 |
IP2X |
1000 |
1000 |
1180 |
TNGR |
6.3 |
3.64 |
2.6 |
1400 |
10 |
IP2X |
1000 |
1000 |
1180 |
TNGR |
6.3 |
3.64 |
2.3 |
1600 |
10 |
IP2X |
1000 |
1000 |
1180 |
10.5KV series neutral grounding resistor selection table,as following:
Type |
Neutral Voltage |
Resistance Value |
Fault Current |
Rated Time |
Protection |
Enclosure |
|||
Line Voltage |
Phase Voltage |
Length |
Width |
High |
|||||
KV |
KV |
[Ω] |
[A] |
[s] |
IP |
[mm] |
[mm] |
[mm] |
|
TNGR |
10.5 |
6.06 |
121.2 |
50 |
10 |
IP2X |
800 |
1000 |
1480 |
TNGR |
10.5 |
6.06 |
60.6 |
100 |
10 |
IP2X |
800 |
1000 |
1480 |
TNGR |
10.5 |
6.06 |
30.3 |
200 |
10 |
IP2X |
800 |
1000 |
1480 |
TNGR |
10.5 |
6.06 |
24.3 |
250 |
10 |
IP2X |
800 |
1000 |
1480 |
TNGR |
10.5 |
6.06 |
20.2 |
300 |
10 |
IP2X |
800 |
1000 |
1480 |
TNGR |
10.5 |
6.06 |
15.2 |
400 |
10 |
IP2X |
1000 |
1000 |
1480 |
TNGR |
10.5 |
6.06 |
12.2 |
500 |
10 |
IP2X |
1000 |
1000 |
1480 |
TNGR |
10.5 |
6.06 |
10.1 |
600 |
10 |
IP2X |
1000 |
1000 |
1480 |
TNGR |
10.5 |
6.06 |
7.6 |
800 |
10 |
IP2X |
1200 |
1000 |
1480 |
TNGR |
10.5 |
6.06 |
6.1 |
1000 |
10 |
IP2X |
1200 |
1000 |
1480 |
TNGR |
10.5 |
6.06 |
5.1 |
1200 |
10 |
IP2X |
1200 |
1000 |
1480 |
TNGR |
10.5 |
6.06 |
4.3 |
1400 |
10 |
IP2X |
1200 |
1000 |
1480 |
TNGR |
10.5 |
6.06 |
3.8 |
1600 |
10 |
IP2X |
1200 |
1000 |
1880 |
TNGR |
10.5 |
6.06 |
3.4 |
1800 |
10 |
IP2X |
1200 |
1000 |
1880 |
20KV series neutral grounding resistor selection table,as following:
Type |
Neutral Voltage |
Resistance Value |
Fault Current |
Rated Time |
Protection |
Enclosure |
|||
Line Voltage |
Phase Voltage |
Length |
Width |
High |
|||||
KV |
KV |
[Ω] |
[A] |
[s] |
IP |
[mm] |
[mm] |
[mm] |
|
TNGR |
20 |
11.55 |
231 |
50 |
10 |
IP2X |
1300 |
2300 |
2300 |
TNGR |
20 |
11.55 |
115.5 |
100 |
10 |
IP2X |
1300 |
2300 |
2300 |
TNGR |
20 |
11.55 |
57.7 |
200 |
10 |
IP2X |
1300 |
2500 |
2300 |
TNGR |
20 |
11.55 |
46.2 |
250 |
10 |
IP2X |
1300 |
2700 |
2300 |
TNGR |
20 |
11.55 |
38.5 |
300 |
10 |
IP2X |
1300 |
2700 |
2300 |
TNGR |
20 |
11.55 |
28.9 |
400 |
10 |
IP2X |
1300 |
2500 |
2300 |
TNGR |
20 |
11.55 |
23.1 |
500 |
10 |
IP2X |
1300 |
2500 |
2300 |
TNGR |
20 |
11.55 |
19.3 |
600 |
10 |
IP2X |
1300 |
2700 |
2300 |
TNGR |
20 |
11.55 |
14.4 |
800 |
10 |
IP2X |
2100 |
2500 |
2000 |
TNGR |
20 |
11.55 |
11.6 |
1000 |
10 |
IP2X |
2100 |
2500 |
2000 |
TNGR |
20 |
11.55 |
9.6 |
1200 |
10 |
IP2X |
2100 |
2500 |
2000 |
TNGR |
20 |
11.55 |
8.3 |
1400 |
10 |
IP2X |
2100 |
2500 |
2000 |
TNGR |
20 |
11.55 |
7.2 |
1600 |
10 |
IP2X |
2100 |
2700 |
2000 |
TNGR |
20 |
11.55 |
6.4 |
1800 |
10 |
IP2X |
2100 |
2700 |
2000 |
TNGR |
20 |
11.55 |
5.8 |
2000 |
10 |
IP2X |
2100 |
2700 |
2000 |
35KV series neutral grounding resistor selection table,as following:
Type |
Neutral Voltage |
Resistance Value |
Fault Current |
Rated Time |
Protection |
Enclosure |
|||
Line Voltage |
Phase Voltage |
Length |
Width |
High |
|||||
KV |
KV |
[Ω] |
[A] |
[s] |
IP |
[mm] |
[mm] |
[mm] |
|
TNGR |
35 |
20.2 |
404.6 |
50 |
10 |
IP2X |
1600 |
2600 |
2524 |
TNGR |
35 |
20.2 |
202.3 |
100 |
10 |
IP2X |
1600 |
2600 |
2524 |
TNGR |
35 |
20.2 |
101.2 |
200 |
10 |
IP2X |
1600 |
2800 |
2524 |
TNGR |
35 |
20.2 |
80.9 |
250 |
10 |
IP2X |
1600 |
3000 |
2524 |
TNGR |
35 |
20.2 |
67.4 |
300 |
10 |
IP2X |
1600 |
3000 |
2524 |
TNGR |
35 |
20.2 |
50.6 |
400 |
10 |
IP2X |
1600 |
2800 |
2524 |
TNGR |
35 |
20.2 |
40.5 |
500 |
10 |
IP2X |
1600 |
2800 |
2524 |
TNGR |
35 |
20.2 |
33.7 |
600 |
10 |
IP2X |
1600 |
3000 |
2524 |
TNGR |
35 |
20.2 |
25.3 |
800 |
10 |
IP2X |
2400 |
2800 |
2144 |
TNGR |
35 |
20.2 |
20.2 |
1000 |
10 |
IP2X |
2400 |
2800 |
2144 |
TNGR |
35 |
20.2 |
16.9 |
1200 |
10 |
IP2X |
2400 |
2800 |
2144 |
TNGR |
35 |
20.2 |
14.5 |
1400 |
10 |
IP2X |
2400 |
2800 |
2144 |
TNGR |
35 |
20.2 |
12.6 |
1600 |
10 |
IP2X |
2400 |
3000 |
2144 |
TNGR |
35 |
20.2 |
11.2 |
1800 |
10 |
IP2X |
2400 |
3000 |
2144 |
TNGR |
35 |
20.2 |
10.1 |
2000 |
10 |
IP2X |
2400 |
3000 |
2524 |
Remark: For other technical parameters & requirements, please contact with our company’s business man.
Stainless steel resistors ,CT is optional(if other equipment like grounding transformer, isolating switch, vacuum contactor and the rated time >10S, the enclosure dimensions will be adjusted )
█ Main Executive Standard
• Specification for neutral-earth resistance in distribution system
• Insulation co-ordination of high voltage transmission and transformation equipment
• Degrees of protection provided by enclosure
• Current transformers
• High-voltage ceramic wall bushings technical specification
• High voltage post insulators ceramic material Part 1: Technical Specification
• High voltage test techniques Part 1: General requirements
• Requirements, Terminology and Test Procedure for Neutral Grounding Devices
█ Ordering Information
1. Rated voltage
2. Rated current
3. Resistance value
4. Rated time
5. Inlet and outlet way
6. Cabinet material、color
7. CT parameter
8. Grounding transformer parameter
9. Class of protection
10. Operating environment
11. Other special requirements, etc.
Product detail pictures:
Related Product Guide:
We also offer you product sourcing and flight consolidation expert services. We've our personal manufacturing unit and sourcing business. We can offer you virtually every variety of merchandise associated to our item range for Wholesale Dealers of Single Phase Load Bank - Neutral Grounding Resistor, NGR EGR – Wepower , The product will supply to all over the world, such as: California, Myanmar, Swiss, Looking forward, we will keep pace with the times, continuing to create new products. With our strong research team, advanced production facilities, scientific management and top services, we will supply high quality products to our customers worldwide. We sincerely invite you to be our business partners for mutual benefits.
By Elsie from Swansea - 2017.10.13 10:47
This manufacturer can keep improving and perfecting products and service, it is in line with the rules of market competition, a competitive company.
By Joyce from Plymouth - 2017.03.07 13:42